Building Technologies Division User Manual LMS14... CC1U7471en
6 The settings in detail 07.05.2014
6.11.12 Electronic temperature controller
Line no. Operating line
2310 Limit thermostat function
Off
On
Limit thermostat function only acts in connection with manual control. In all other
operating situations, the function is deactivated.
Off
When the Limit thermostat function is deactivated, the maximum switch-off point is
limited to the limit thermostat’s cutout temperature –3 K, the maximum setpoint to the
limit thermostat’s cutout temperature –3 K – switch-off threshold.
On
When the Limit thermostat function is activated, maximum switch-off point and
maximum setpoint are limited to the limit thermostat’s cutout temperature –3 K.
Line no. Operating line
2531 Cutout temp LT
Limit thermostat
function
A
dditional parameters