6.11.33 Additional settings for static pressure supervision
Line no. Operating line
[4197.1] Outp’reduc press’swit
Off
On
When this function is activated and the pressure drops below the water pressure
threshold Hx minimum, the LMS14 responds by reducing the output by 20% in relation
to the current output. Also refer to chapter Static pressure supervision.
Off
Function is deactivated.
On
Function is activated.
6.11.34 Additional settings for dynamic pressure supervision
Line no. Operating line
[4198.1] DynPress pump delay
0…10 s; resolution 0.2 s
For function of this parameter, refer to section Basics of dynamic supervision.
Line no. Operating line
[4199.1] DynPress repetitions
0…10; resolution 1
For function of this parameter, refer to section Basics of dynamic supervision.
Line no. Operating line
[4200.1] Dyn Press pause
0…1200; resolution 0.2 s
For function of this parameter, refer to section Basics of dynamic supervision.
Line no. Operating line
[4201.1] DynPress warn offset
0…1 bar; resolution 0.1 bar
For function of this parameter, refer to section Basics of dynamic supervision.
Line no. Operating line
[4202.1] DynPress AutoActive
Off
On
For function of this parameter, refer to section Basics of dynamic supervision.
Off
Function is deactivated.
On
Function is activated.
Outp’reduc press’swit
DynPress pump delay
DynPress repetitions
Dyn Press pause
DynPress warn offset
DynPress AutoActive