SINAMICS Integrated type
For SIMOTION D410‑2, the type is always SINAMICS S120 Integrated.
Version of the SINAMICS Integrated
Depending on the selected SIMOTION version, several versions are available for the
SINAMICS
Integrated. Please note that separate SIMOTION D firmware is available for each
version of the SINAMICS Integrated.
Configuring the PROFINET interface
After you have acknowledged the "Insert SIMOTION Device" dialog with "OK", the "Properties
- Ethernet Interface" dialog box opens in the case of a D410‑2 DP/PN.
If you are using the PROFINET interface, set the interface properties in the "Properties -
Ethernet Interface" dialog box.
To this end, proceed as follows:
1. Click the "New" button.
The "New Subnet Industrial Ethernet" dialog box opens. Rename the new subnet, or accept
the default name by clicking "OK".
2. Select the new Ethernet subnet, which is now displayed in the "Properties - Ethernet
Interface" dialog box.
3. Enter the required addresses in the "IP address" and "Subnet mask" fields of the "Properties
- Ethernet Interface" dialog box. Under "Gateway", define whether you are going to use a
router and, if yes, enter the router address. Confirm with "OK".
Result
If you have not yet configured a PG/PC in your project, you can select the interface for the PG/
PC connection now.
6.2.2 Configuring the PROFIBUS PG/PC interface
Requirements
The following requirements must be satisfied in order to configure the PG/PC interface:
● You have completed the "Insert SIMOTION Device" dialog box with "OK"
● A PG/PC has not yet been configured in the project.
If these requirements have been satisfied, you can configure the interface for the PG/PC
connection in the "Interface Selection ‑ D410" dialog box.
Parameter assignment / addressing
6.2 Creating a project and configuring the communication
SIMOTION D410-2
106 Commissioning and Hardware Installation Manual, 01/2015