5.7 Fan
5.7.1
Cooling the SIMOTION D410-2
Overview
A fan is always required for operation of the SIMOTION D410-2. This is included in the scope
of delivery of the D410-2 control unit. The fan operates temperature-controlled and is switched
on depending on the air intake temperature and the CPU load.
Fan faults
Fan faults are indicated as follows:
Entry in diagnostic buffer
Indicated via system variable
Calling the PeripheralFaultTask
If a fan fault occurs or the fan is unplugged, the module continues to run. The controller goes
into FAULT state when overtemperature occurs (temperature threshold 2 exceeded), whereby
all LEDs flicker red. The state can only exited through power off/on
For further information on the evaluation of fan faults, see Section Overview of fan states
(Page 99).
5.7.2 Overview of fan states
Evaluation of fan faults
SIMOTION D410-2 has a single fan.
Fan faults are detected through a cyclic fan test or when a malfunction is determined when
the fan is activated (fan does not rotate or fan rotates at too low a speed).
Fan faults are signaled by the following diagnostic buffer entry:
Fan on the module is defective.
Commissioning (hardware)
5.7 Fan
SIMOTION D410-2
Commissioning and Hardware Installation Manual, 01/2015 99

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D410-2 DP and is the answer not in the manual?

Siemens SIMOTION D410-2 DP Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D410-2 DP
CategoryController
LanguageEnglish

Related product manuals