No. Information Data Class
(Type)
Type
_:2731:52 General:Behavior O
_:2731:53 General:Health O
Binary IO
_:10081:300 Slow-scan 1:Start record C
_:10081:502 Slow-scan 1:>External start I
_:10081:503 Slow-scan 1:>Manual start I
_:10081:310 Slow-scan 1:Fault number O
_:10081:311 Slow-scan 1:Recording started O
_:10081:314 Slow-scan 1:Record made O
_:10081:322 Slow-scan 1:Recorder formatted O
Continuous Recorder
Overview of Functions
Continuous recorders are used for data acquisition of the measured values over a longer time period. Thus,
long-time analyses of the power system behavior can be performed. The continuous recorder forms the arith-
metic average value over the averaging time.
Structure of the Function
The function Continuous recorder is preconfigured once at the factory. Within the Recorder function group,
the Continuous recorder can be operated a maximum of 5 times.
[dwcont7k-161012-01.tif, 2, en_US]
Figure 7-29 Structure/Embedding of the Function
Function Description
The continuous recorder is not a triggered recorder, runs constantly, and has large averaging times. The
continuous recorder saves the arithmetic average value of the process quantities (power, frequency, RMS
values of the fundamental component of currents, voltages and symmetric components).
In the course of parameterization, specify a maximum memory capacity for storage of the recordings. The
continuous recorder is organized as a ring buffer. When the memory is filled completely, the oldest data are
overwritten automatically.
Mode
The continuous recorder operates only if Mode is set to on .
The recording is interrupted if Mode is set to off during the recording. Recording starts again if Mode is set
to on again.
7.2.8
7.2.8.1
7.2.8.2
7.2.8.3
Fault Recorder
7.2 Function-Group Type Recorder
SIPROTEC 5, Fault Recorder, Manual 247
C53000-G5040-C018-5, Edition 11.2017