Figure 3-8
Indication Configuration in DIGSI 5 (Example: User-Defined Log V1/2)
Sequence of Events Log
The change of the status of binary signals (SPS) is stored in chronological sequence in the Sequence of
events log.
Violation of an upper or lower limiting value is also recorded as an event. Up to 2000 entries can be stored in
the list. Upon reaching the maximum number of entries, the oldest entries will be overwritten.
Reading from the PC with DIGSI 5
•
Use the project tree window to access the sequence of events for your SIPROTEC 5 device.
Project → Device → Process Data → Logs → Sequence of events
•
The sequence of events log is shown to you in the last loaded state from the device. To update the device
(synchronization with the device), click the button Read log entries in the headline of the indication list
(see the following figure).
3.1.5.4
System Functions
3.1 Indications
52 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017