Addr. Parameter C Setting Options Default Setting
_:9571:113 Trig. V fund 1:Max.
trigger hysteresis
0.900 p.u. to 0.990 p.u. 0.980 p.u.
_:9571:102 Trig. V fund 1:Min.
trigger active
•
no
•
yes
yes
_:9571:106 Trig. V fund 1:Min.
trigger
0.300 V to 340.000 V 80.000 V
_:9571:114 Trig. V fund 1:Min.
trigger hysteresis
1.010 p.u. to 1.100 p.u. 1.020 p.u.
_:9571:103 Trig. V fund 1:dM/dt rise
active
•
no
•
yes
no
_:9571:107 Trig. V fund 1:dM/dt rise
(/Filter time)
0.300 V to 340.000 V 20.000 V
_:9571:115 Trig. V fund 1:dM/dt rise
hysteresis
0.900 p.u. to 0.990 p.u. 0.980 p.u.
_:9571:104 Trig. V fund 1:dM/dt
drop active
•
no
•
yes
no
_:9571:108 Trig. V fund 1:dM/dt
drop (/Filter time)
0.300 V to 340.000 V 20.000 V
_:9571:116 Trig. V fund 1:dM/dt
drop hysteresis
0.900 p.u. to 0.990 p.u. 0.980 p.u.
_:9571:112 Trig. V fund 1:Filter time 2 cycles to 250 cycles 2 cycles
Information List
No.
Information Data Class
(Type)
Type
Trig. V RMS 1
_:9601:54 Trig. V RMS 1:Inactive SPS O
_:9601:52 Trig. V RMS 1:Behavior ENS O
_:9601:53 Trig. V RMS 1:Health ENS O
_:9601:301 Trig. V RMS 1:Trigger active SPS O
Trig. V fund 1
_:9571:54 Trig. V fund 1:Inactive SPS O
_:9571:52 Trig. V fund 1:Behavior ENS O
_:9571:53 Trig. V fund 1:Health ENS O
_:9571:301 Trig. V fund 1:Trigger active SPS O
Current Trigger
Overview of Functions
Current triggers start with exceeding or dropping below the set limiting values (level and gradient trigger) in
the fast-scan and slow-scan recorders. It is triggered by fundamental values, RMS values, or on symmetrical
components.
Structure of the Function
The Current trigger function can be configured in the Voltage/current 1-phase function group. The structure
of the Current trigger function is shown in the following figure:
7.4.1.7
7.4.2
7.4.2.1
7.4.2.2
Fault Recorder