Figure 7-45 dM/dt
dM Change of the measurand
dt Change of the filter time
Function Description Binary Trigger
Manual Trigger Start
The fast-scan recorder and the slow-scan recorder can be manually triggered.
They can trigger the start of the recording as follows:
•
Manually by the fault recorder (function key on the operation panel)
•
Via DIGSI 5
•
Via any IEC 61850 client (e.g., SICAM PQS with IEC 61850)
NOTE
The manual trigger is started by pressing the function keys routed to the >Manual start. In the applica-
tion templates, Function key 1 is the default for the fast-scan recorder and Function key 2 is the default
for the slow-scan recorder (see Figure 7-49).
The record time depends on the configured value Manual record time for the manual trigger start.
Manual Start of the Trigger with Information Routing
For the fast-scan recorder and the slow-scan recorder, you route the manual trigger start in the Information
routing in the matrix row >Manual start to the inputs that can be assigned binary signals.
[scmantrm-280113-01.tif, 1, en_US]
Figure 7-46 Routing the Manual Trigger Start
7.3.3
7.3.3.1
Fault Recorder
7.3 Function Description Analog and Binary Triggers
SIPROTEC 5, Fault Recorder, Manual 265