Addr. Parameter C Setting Options Default Setting
_:10021:106 Trigger Ssum 1:Min.
trigger
1 A @ 100 Irated 0.36 VA to 60000.00 VA 138.56 VA
5 A @ 100 Irated 1.80 VA to 300000.00 VA 692.82 VA
_:10021:114 Trigger Ssum 1:Min.
trigger hysteresis
1.010 p.u. to 1.100 p.u. 1.020 p.u.
_:10021:103 Trigger Ssum 1:dM/dt
rise active
•
no
•
yes
no
_:10021:107 Trigger Ssum 1:dM/dt
rise (/Filter time)
1 A @ 100 Irated 0.36 VA to 60000.00 VA 34.64 VA
5 A @ 100 Irated 1.80 VA to 300000.00 VA 173.21 VA
_:10021:115 Trigger Ssum 1:dM/dt
rise hysteresis
0.900 p.u. to 0.990 p.u. 0.980 p.u.
_:10021:104 Trigger Ssum 1:dM/dt
drop active
•
no
•
yes
no
_:10021:108 Trigger Ssum 1:dM/dt
drop (/Filter time)
1 A @ 100 Irated 0.36 VA to 60000.00 VA 34.64 VA
5 A @ 100 Irated 1.80 VA to 300000.00 VA 173.21 VA
_:10021:116 Trigger Ssum 1:dM/dt
drop hysteresis
0.900 p.u. to 0.990 p.u. 0.980 p.u.
_:10021:112 Trigger Ssum 1:Filter
time
2cyclesto250 cycles 2 cycles
Trigger Psw #
_:1 Trigger Psw #:Mode
•
off
•
on
•
test
off
_:100 Trigger Psw #:X reach 1 A 0.100 Ω to 600.000 Ω 100.000 Ω
5 A 0.020 Ω to 120.000 Ω 20.000 Ω
_:101 Trigger Psw #:R (ph-g) 1 A 0.100 Ω to 600.000 Ω 100.000 Ω
5 A 0.020 Ω to 120.000 Ω 20.000 Ω
_:102 Trigger Psw #:R (ph-ph) 1 A 0.100 Ω to 600.000 Ω 200.000 Ω
5 A 0.020 Ω to 120.000 Ω 40.000 Ω
Information List
No.
Information Data Class
(Type)
Type
Trigger Psum 1
_:9901:54 Trigger Psum 1:Inactive SPS O
_:9901:52 Trigger Psum 1:Behavior ENS O
_:9901:53 Trigger Psum 1:Health ENS O
_:9901:301 Trigger Psum 1:Trigger active SPS O
Trigger Qsum 1
_:9961:54 Trigger Qsum 1:Inactive SPS O
_:9961:52 Trigger Qsum 1:Behavior ENS O
_:9961:53 Trigger Qsum 1:Health ENS O
_:9961:301 Trigger Qsum 1:Trigger active SPS O
Trigger Ssum 1
_:10021:54 Trigger Ssum 1:Inactive SPS O
_:10021:52 Trigger Ssum 1:Behavior ENS O
_:10021:53 Trigger Ssum 1:Health ENS O
_:10021:301 Trigger Ssum 1:Trigger active SPS O
7.5.4.10
Fault Recorder
7.5 Trigger Functions 3-Phase
346 SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017