7:2.4.10Sequence start
The sequence start function can be used for starting several
motors or multiple speed motors with different parameter sets
such as individual ramp times, initial voltages, current limits
etc.
Up to three individual parameter sets can be used
simultaneously.
The LOCAL CONTROL menu can not be entered if Sequence
start is selected.
Number of sequences (No of Seq)
To set parameters related to a sequence start, enter the Seq
Start group.
Select the required number of parameter sets for the
application.
The following selections are available:
No Sequence start is not activated.
The softstarter is in normal operation.
2 Two different parameter sets will be used.
3 Three different parameter sets will be used.
Press Store to save/activate the selected function.
First sequence setting current (1st Set Ie)
Set the current for the first parameter group and press Store
to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.
Second sequence setting current (2nd Set Ie)
Set the current for the second parameter group.
Press Store to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.
If sequence start was used and the parameter No of Seq is
changed to No, the overload protection will automatically be
set to Normal independent of earlier setting.