Functions
Chapter 10
149
1SFC132003M0201
10:34 High current protection, type of
operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/High I/High I Op
This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the high current protection is
selected.
Stop–M The motor stops and a manual reset is required
before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears.
Ind The motor continues to run but a fault indication
is given.
10:35 Phase reversal protection
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Phase Rev
The softstarter accepts any phase sequence but if this
protection is selected, the phase sequence must be L1, L2,
L3, or else the protection is activated.
Parameter
text
Default value Setting range Description
High I Op Stop–M Stop–M, Stop–A,
Ind
Type of opera-
tion for high cur-
rent protection
Parameter
text
Default value Setting range Description
Phase Rev No Yes, No Phase reversal
protection