Functions
Chapter 10
168
1SFC132003M0201
10:67 Initial voltage, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Init Volt1
This parameter makes it possible to set the initial voltage for
the first parameter set
10:68 Current limit, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Curr Lim1
This parameter makes it possible to set the current limit level
for the first parameter set.
10:69 Setting current, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./1st Set Ie
This parameter makes it possible to set the rated motor
current for the first parameter set
Parameter
text
Default value Setting range Description
Init Volt1 30% 30...70% First sequence,
initial voltage for
start ramp
Parameter
text
Default value Setting range Description
Curr Lim1 4 x I
e
2.0...7.0 x I
e
First sequence,
current limit
Parameter
text
Default value Setting range Description
1st Set Ie Ir 9...1207A divided
into 19 overlap-
ping ranges
First sequence,
motor rated cur-
rent