Description
Chapter 3
26
1SFC132003M0201
3:6 Environmental influence
The product is designed to minimize the environmental
affects during manufacturing and use of the product. Most of
the materials used, are of recycle type and shall be handled
and recycled according to existing laws.
Further information regarding used material and recycling of
the product can be found at:
www.abb.com/lowvoltage
3:7 Specifications
Degree of protection
(Main circuit)
IP 10 for PST30...72
IP 00 for PST85...1050
Operating position Vertical at
± 10°
Ambient temperature Storage: -25 °C to +70 °C (-13 °F to 158 °F)
Operation: 0
°C to +40 °C (32 °F to 104 °F
without derating
+40
°C to +50 °C (104 °F to 122 °F)
with derating 0.8% / °C (0.8%/ 33.8°F)
Altitude 1000 m (3281 ft.) above sea level without derating
1000 - 4000 m (3281 - 13123 ft.) with derating 0.007% /m
Pollution degree 3
Relative humidity 5 - 95% (non condensing)
Standards IEC 60947-1
IEC 60947-4-2
EN 60947-1
EN 60947-4-2
Standards UL UL508
PTC input IEC 60947-8 Mark A detectors
DIN 44081 and DIN 44082
Marine approvals Contact your ABB sales office