Functions
Chapter 10
167
1SFC132003M0201
10:65 Sequence start, number of
sequences
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/No of Seq
The softstarter can start motors with up to three different
parameter sets (1st parameter set, 2nd parameter set and
3rd parameter set). This function can be used for starting
motors in a sequence (one by one) and also for starting two
or three speed motors where different starting parameters
are required for each speed.
The LOCAL CONTROL menu can not be entered if Sequence
start is selected.
10:66 Start ramp, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Start Ramp1
This parameter makes it possible to set the start ramp time
for the first parameter set.
Parameter
text
Default value Setting range Description
No of Seq No No, 2, 3 Number of
sequences for
sequence start.
Parameter
text
Default value Setting range Description
Start
Ramp1
10 s 1...30s, 1...120s First sequence,
time for start
ramp