Functions
Chapter 10
169
1SFC132003M0201
10:70 Start ramp, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Start Ramp2
This parameter makes it possible to set the start ramp time
for the second parameter set.
10:71 Initial voltage, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Init Volt2
This parameter makes it possible to set the initial voltage for
the second parameter set.
10:72 Current limit, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Curr Lim2
This parameter makes it possible to set the current limit level
for the second parameter set.
Parameter
text
Default value Setting range Description
Start
Ramp2
10 s 1...30s, 1...120s Second
sequence, time
for start ramp
Parameter
text
Default value Setting range Description
Init Volt2 30% 30...70% Second
sequence, ini-
tial voltage for
start ramp
Parameter
text
Default value Setting range Description
Curr Lim2 4 x I
e
2.0...7.0 x I
e
Second
sequence, cur-
rent limit