Functions
Chapter 10
171
1SFC132003M0201
10:76 Current limit, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Curr Lim3
This parameter makes it possible to set the current limit level
for the third parameter set.
10:77 Setting current, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq. Start/3rd Seq. Param./3rd Set Ie
This parameter makes it possible to set the rated motor
current for the third parameter set.
Parameter
text
Default value Setting range Description
Curr Lim3 4 x I
e
2.0...7.0 x I
e
Third sequence,
current limit
Parameter
text
Default value Setting range Description
3rd Set Ie Ir 9...1207A divided
into 19 overlap-
ping ranges
Third sequence,
motor rated cur-
rent