EasyManuals Logo

ABB PST72 Installation And Commissioning Manual

ABB PST72
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #164 background imageLoading...
Page #164 background image
Functions
Chapter 10
164
1SFC132003M0201
10:61 Fieldbus control
Path in menu:
Menu/SETTINGS/Functional Settings/
Fieldbus/Fieldb Ctrl
If the softstarter is going to be used with fieldbus
communication, the fieldbus interface must be activated
before any action can be taken.
Caution!
The motor may start unexpectedly if there is a start signal
present when doing any of the actions listed below.
Parameter
text
Default value Setting range Description
I Range
Max
PST(B) size
dependent
10...20000 A Upper limit for
the current for
the analog out-
put
U Range
Max
600 V 10...1000 V Upper limit for
the voltage for
the analog out-
put
kW Range
Max
PST(B) size
dependent
1...3000 kW Upper limit for
the active power
for the analog
output
hp Range
Max
PST(B) size
dependent
1...4000 hp Upper limit for
the active power
for the analog
output
Q Range
Max
PST(B) size
dependent
1...3000 kVAr Upper limit for
the reactive
power for the
analog output
S Range
Max
PST(B) size
dependent
1...3000 kVA Upper limit for
the apparent
power for the
analog output

Table of Contents

Other manuals for ABB PST72

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PST72 and is the answer not in the manual?

ABB PST72 Specifications

General IconGeneral
BrandABB
ModelPST72
CategoryController
LanguageEnglish

Related product manuals