D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide |
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 148
Using Zonex Bus 1 exclusively for fire
devices and Zonex Bus 2 exclusively for
non-fire devices is acceptable.
Install all D8128D OctoPOPIT Modules
used for fire devices within the control
panel enclosure or in a separate
enclosure in the same room within 6.1
m (20 ft) of the main control panel.
Route all Zonex bus wiring in EMT
(electrical metallic tubing) conduit.
For system supervision, do not use
looped wire terminals.
D8129 Octo-relay Modules
If any fire devices are connected to
Zonex Bus 1 (or Zonex Bus 2), you must
use all D8129 OctoRelay Modules
connected to Zonex Bus 1 (or Zonex
Bus 2) only for fire applications.
Install all D8129 OctoRelay Modules
used for fire devices shall be mounted
in the same enclosure with the control
panel, or in a separate enclosure in the
same room connected by conduit no
more than 20 ft (6 m) of the panel.
To meet UL 864, route all Zonex bus
wiring in EMT (electrical metallic
tubing) conduit.
19.2.3 SDI2 Bus Devices
D9412GV4/D7412GV4 v2.03 Control Panels
can support a number of accessory devices
from the SDI2 Bus using Terminals 33 through
36. Some devices include the B208, B308,
B420, B426, B450, B520, B915, B920, B921C,
B930, B942/B942W, B810 and B820.
B208 Octo-input Module
Do not connect fire and non-fire
devices to the same B208 Octo-input
Module.
B208 Octo-input module is fully
supervised.
B308 Octo-output Module
Do not connect fire and non-fire
devices to the same B308 Octo-input
Module.
B420 Ethernet Communication Module
Only two devices can be installed at
one time.
B426 Ethernet Communication Module
Only two devices can be installed at
one time.
B450 Plug-in Communicator Interface
Only two devices can be installed per
control panel.
B450 must have a B44x Plug-in Cellular
Communicator inserted in order to be
operational.
B520 Auxiliary Power Supply Module
A total of 8 modules can be installed at
one time.
B915 Basic Keypad
Any total combination of 16 keypads
can be installed on SDI2.
B920 Two-line Alphanumeric Keypad
Any total combination of 16 keypads
can be installed on SDI2.
B921C Two-line Capacitive Keypad with
Inputs
Any total combination of 16 keypads
can be installed on SDI2.
B920 Two-line Alphanumeric Keypad
Any total combination of 16 keypads
can be installed on SDI2.
B942/B942W Touch Screen Keypad
Any total combination of 16 keypads
can be installed on SDI2.
B810 receiver
For the B810 (RADION receiver SD) and
B820 (SDI2 Inovonics Interface
Module), only one device can be
installed on a control panel.
B820 SDI2 Inovonics Interface Modules
For the B810 (RADION receiver SD) and
B820 (SDI2 Inovonics Interface
Module), only one device can be
installed on a control panel.

Table of Contents

Other manuals for Bosch D9412GV4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch D9412GV4 and is the answer not in the manual?

Bosch D9412GV4 Specifications

General IconGeneral
Power Supply12 VDC
TypeControl Panel
ModelD9412GV4
ManufacturerBosch
Operating Temperature0°C to +49°C (+32°F to +120°F)
Compatible withConettix IP, GSM, GPRS, and POTS communicators

Related product manuals