D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.0 Approved Applications
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 94
17.4.7 UL Listed Synchronization (Sync) Modules and Strobes Compatible with the
D9412GV4/D7412GV4
To be UL 864 9
th
edition compliant, you must use only these models of synchronization
modules and strobes with the D9412GV4 and D7412GV4 Control Panels.
Wheelock maximum control panel powered devices: 4
Wheelock maximum 12 VDC external powered devices: 11
Wheelock maximum 24 VDC external powered devices 33
System Sensor maximum control panel powered devices 4
System Sensor maximum 12 VDC external powered devices 11
System Sensor maximum 24 VDC external powered devices 33
These are the maximum number of devices; high-current setting reduces this quantity.

Table of Contents

Other manuals for Bosch D9412GV4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch D9412GV4 and is the answer not in the manual?

Bosch D9412GV4 Specifications

General IconGeneral
Power Supply12 VDC
TypeControl Panel
ModelD9412GV4
ManufacturerBosch
Operating Temperature0°C to +49°C (+32°F to +120°F)
Compatible withConettix IP, GSM, GPRS, and POTS communicators