D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.0 Approved Applications
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 93
17.4.6 UL Listed Two-Wire Smoke Detectors Compatible with the D125B
A D125B Powered Loop Interface Module is required to connect smoke detectors to the on-board
points (1-8).
Table 34: Two-wire smoke detector compatibility table
Manufacturer CTN Series Base Reversing* Maximum number of detectors
per loop
12 V 24 V
Bosch D263 D263 N/A 8 8
D263TH 8 8
D263THC 8 8
D263THS ● 8 8
D285 D285 D287, D288,
D340
10 10
D285TH 10 10
F220-P F220 F220-B6 8 8
F220-PTH 8 8
F220-PTHC 8 8
F220-135 8 8
F220-135F 8 8
F220-190F 8 8
System Sensor 2W-B i3 N/A 8 8
2WTA-B 8 8
2WT-B 8 8
5151 100 B110LP 10 10
* D132A does not operate at 24 V; use only on 12 V powered loops.