Required gen-set power factor when the group of gen-sets is running
parallel to the mains. The PF is regulated locally in each controller by PF
control regulation loop, VARsharing is not active.
NONE, FORWARD, REVERSE, BOTH [-]
Enables or disables forward/reverse synchronization (according to SPtM /
MINT versions).
No synchronizing is enabled. (SPtM and MINT)
GCB synchronizing is enabled. (SPtM and MINT)
MCB synchronizing is enabled. (SPtM)
GCB and MCB synchronizing are enabled. (SPtM)
PeakLevelStop ... 32000 [kW]
Load consumption level the gen-set has to start at. Function is inactive when
PeakAutS/S Del = OFF. Gen-set start is “PeakAutS/S Del” delayed after the
consumption of the Load exceeds the PeakLevelStart limit.
NOTE:
The actual setpoint units and range depend on setting of the Power format
(see the LiteEdit manual).
NOTE:
It is necessary to use IC-NT CT-BIO7 module and measure 1Ph Mains
current.