Setpoint: #SysPwrFactor
Group
Process Control
Range [units]
0.7 ... 1.0 [-]
Related
applications
MINT
Description
Required gen-set power factor when the group of gen-sets is running
parallel to the mains. The PF is regulated locally in each controller by PF
control regulation loop, VARsharing is not active.
Setpoint: Synchro Enable
Group
ProcessControl
Range [units]
NONE, FORWARD, REVERSE, BOTH [-]
Related
applications
All
Description
Enables or disables forward/reverse synchronization (according to SPtM /
MINT versions).
NONE
No synchronizing is enabled. (SPtM and MINT)
FORWARD
GCB synchronizing is enabled. (SPtM and MINT)
REVERSE
MCB synchronizing is enabled. (SPtM)
BOTH
GCB and MCB synchronizing are enabled. (SPtM)
Setpoint: PeakLevelStart
Group
Process Control
Range [units]
PeakLevelStop ... 32000 [kW]
Related
applications
SPtM
Description
Load consumption level the gen-set has to start at. Function is inactive when
PeakAutS/S Del = OFF. Gen-set start is PeakAutS/S Del delayed after the
consumption of the Load exceeds the PeakLevelStart limit.
NOTE:
The actual setpoint units and range depend on setting of the Power format
(see the LiteEdit manual).
NOTE:
It is necessary to use IC-NT CT-BIO7 module and measure 1Ph Mains
current.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals