0 ... PeakLevelStart [kW]
Load consumption level the gen-set has to stop at. Gen-set stop is
“PeakAutS/S Del” delayed after PeakLevelStop limit is reached. Load
consumption is calculated (not directly measured) as a sum of gen-set and
mains active power.
NOTE:
The actual setpoint units and range depend on setting of the Power format
(see LiteEdit manual).
NOTE:
It is necessary to use IC-NT CT-BIO7 module and measure 1Ph Mains
current.
The condition for the “peak” automatic start or stop must be valid for a period
longer than the value of this setpoint to execute the automatic start or stop.
Adjusting to “0” causes stop of the gen-set (if there is no other demand for
running) and disables the automatic peak shaving start.