InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
192
Setpoint: #LoadResStop 1
Group
Power Management
Range [units]
LoadResStrt 1 ... 32000 [#PowerMgmtMode dependent]
Related
applications
MINT
Description
This setpoint adjusts the reserve for stop if the set 1 of reserves is selected,
i.e. binary input Load Reserve 2 is not active. See the power management
description to learn more about reserves.
Setpoint: #LoadResStrt 2
Group
Power Management
Range [units]
-32000 ... LoadResStop 2 [#PowerMgmtMode dependent]
Related
applications
MINT
Description
This setpoint adjusts the reserve for start if the set 2 of reserves is selected,
i.e. binary input Load Reserve 2 is active. See the power management
description to learn more about reserves.
Setpoint: #LoadResStop 2
Group
Power Management
Range [units]
LoadResStrt 2 ... 32000 [#PowerMgmtMode dependent]
Related
applications
MINT
Description
This setpoint adjusts the reserve for stop if the set 2 of reserves is selected,
i.e. binary input Load Reserve 2 is active. See the power management
description to learn more about reserves.
Setpoint: #MinRun Power
Group
Power Management
Range [units]
0 ... 65000 [kW]
Related
applications
MINT
Description
In case of activation LBI MinRunPower -> based on the nominal power, the
gen-sets needed for equalizing the actual MinRunPower requirement are
started (or kept running even if stop reserve is fulfilled). Note, that LBI’s Min
Run Power needs to be activated on all gen-sets in the same time.
Setpoint: #NextStrt Del
Group
Power Management
Range [units]
0 ... 3600 [s]
Related
applications
MINT
Description
This setpoint adjusts the delay for starting the next gen-set after the reserve
has dropped below the reserve for start.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals