EasyManuals Logo
Home>ComAp>Controller>InteliCompact NT

ComAp InteliCompact NT Reference Guide

ComAp InteliCompact NT
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #203 background imageLoading...
Page #203 background image
InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
203
Setpoint: GCB Open Del
Group
Sync/Load Ctrl
Range [units]
Load Ramp ... 1800 [s]
Related
applications
All
Description
Use this setpoint to adjust the timeout for reaching the load level GCB Open
Level during the gen-set is being unloaded. When the timeout has elapsed,
the GCB will open regardless of the load.
Setpoint: Sync Timeout
Group
Sync/Load Ctrl
Range [units]
1 ... 1800 [s]
Related
applications
All
Description
This setpoint adjusts the maximum duration of synchronizing. If
synchronizing is not successful within this period of time, the Sync Timeout
or RevSyncTimeout alarm will be issued.
Setpoint: LoadShare Gain
Group
Sync/Load Ctrl
Range [units]
0 ... 200.0 [%]
Related
applications
MINT
Description
Gain of the load sharing control PI loop.
Setpoint: LoadShare Int
Group
Sync/Load Ctrl
Range [units]
0 ... 100 [%]
Related
applications
MINT
Description
Relative integration factor of load sharing control loop.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals