*Refer to Table 6-16, Table 6-17 on
page 74 and Table 6-18 on page 75 for
technical data and part numbers.
**Refer to Table 6-2, Table 6-3, Table 6-4
and Table 6-5 on page 68 for technical
data and part numbers.
***Fuses are needed only if the power
supply has a current rating of more than
10A.
****Refer to section 14.1.3 Supply
requirements on page 267 for supply
requirements.
Current sharing between drives
whose motor outputs are
connected in parallel
When used from a 3 phase supply, it is
preferable not to link the DC bus because
the impedance between DC and each
inverter output is just the impedance of
the output chokes. Also, on the input
side, input current sharing is determined
only by making the temperature of the
two rectifiers similar and by ensuring that
both rectifiers see the same impedance
to the line power supply.