Emerson Process Management GmbH & Co. OHG A-37
X-STREAM XE
Instruction Manual
HASXEE-IM-HS
10/2012
A
Appendix
PLCQuickReferenceCard
Rev.2010‐10
PLCQuickReferenceCard
Programlinesnottoexceed100chars,otherwiseruntimeerrorsshowup!
Firstprogramlinetostartwith####,otherwiseuploadtoanalyzerfails!
Iftimersneedtobeused,theyhavetobesetupatthebeginningoftheprogram(seeExampleProgram
)
ForUSBtransfersavePLC.TXTontheUSBstickintothedirectory
emerson_xe\<Analyzer Serial Number>\config
PLCTimerSetup
Syntax:<COMMAND> <ID> <VALUE>; [Comment]
FordetailsseeTimerModes
below
COMMAND ID VALUE
TMR_MODE 1…8 OFFDELAY,ONDELAY,REPPULSE,SINGLEPULSE,
RETRIGSPULS E,INHIBSPULSE,CLKTRGPULSE,
COUNTER
TMR_DURATION 1…8 1...3600
TMR_PERIOD_CNT 1…8 1...3600
(REPPULSE:sec
CLKTRGPULSE:min
COUNTER:counts)
TMR_TRIG_TIME 1…8 YYYY,MM,DD,hh,mm
SequencerSetup
Syntax:<COMMAND> <ID> <VALUE>; [Comment]
FordetailsseeSequencerFunctionBlock
below
COMMAND ID VALUE DESCRIPTION
SEQ_DURATION 1…4 1…3600 Setswitchduration
SEQ_STAB_TIME 1…4 0…3599,
butmax.(<SEQ_DURATION>‐1)
Setstabilizationtime
SEQ_NUM_OUTS 1…4 2…10 Setno.ofoutputstobeused
SEQ_SNGL_CYCLE 1…4 TRUE,FALSE Setsinglecyclemode
ProgrammingQuickReference
Syntax:<OPERATOR> [<OPERAND>,<OPERAND>,…]; [Comment]
Maximumamountofoperators&operands:approx.400
SPECIALCHARACTER Function
, SeparationofOperands
; CommandTermination
# StartofCommentLine
A.7 PLC Quick Reference
A.7 PLC Quick Reference