CHAPTER 4: SETPOINTS DEVICE
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–13
Security
The following security features are available:
• Basic Secu
rity – The basic security feature present in the default offering of the
product.
• CyberSentr
y – The feature refers to the advanced security options available as a
software option. When this option is purchased, it is automatically enabled and Basic
Security is disabled.
GENERAL RULES FOR ROLES
• All the roles are password protected, except for the Observer role which is user
def
ined on the device. A user with Observer capability defined on the Radius is
password protected.
• All the roles, except for the Observer role, suppor
t only one session at one time.
• The Observer role has read-only access to all values in the relay except for one service
comm
and which is described in the Password Recovery Procedure section.
• All the roles, except for the Observer, have access to a “log out” setting, which has the
effe
ct of switching to Observer role.
• A Setpoint access setting for bypassing security is
available. If this feature is used, the
user gains total access for any operations / configuration changes executed either
from the front panel or from EnerVista.
• The setpoint access setting may be either swi
tched directly on or assigned to a digital
input.
• If the setpoint access setting is assigned to a digital input, the digital input needs to be
act
ivated through a physical key (jumper).
• The setpoint access setting may be
set only by an Administrator.
PASSWORD COMPLEXITY
The password complexity is available on both Basic Security and CyberSentry.
If password complexity is enabled, a user account requires an alpha-numeric password
that me
ets the following requirements:
• Passwords cannot contain the user account name or parts of the user's full name that
ex
ceed two consecutive characters
• Passwords must be 6 to 20 characters in length
• Passwords must contain characters from three of the following four categories:
- English uppercase characters (A through Z)
- English lowercase characters (a through z)
- Base 10 digits (0 through 9)
- Non-alphabetic characters (for ex
ample, ~, !, @, #, $,%, &)
PASSWORD RECOVERY PROCEDURE
In the event of losing all passwords, the 869 can be reset to factory defaults by following
the p
rocedure below:
1. The customer sends an email to the customer support department providing a valid
serial number and using a recognizable corporate email account.
2. Customer support provides the customer with the code to reset the relay to factory
defaults.
3. The customer enters the code provided from the front panel, under the menu
Setpoints > Device > Installation > Service Command
and resets the relay to factory
defaults.
NOTE:
Note that even an Observer may execute this operation.