EasyManuals Logo

GE MI-869 User Manual

GE MI-869
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #310 background imageLoading...
Page #310 background image
4–192 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Neutral
Instantaneous
Overcurrent
Protection
The 869 Neutral Instantaneous Overcurrent protection element computes the neutral
current (In) using the following formula:
|In| = |Ia + Ib + Ic|
The element essentially responds to the magnitude of
a neutral current fundamental
frequency phasor calculated from the phase currents. A positive-sequence restraint is
applied for better performance. A small portion (6.25%) of the positive-sequence current
magnitude is subtracted from the zero-sequence current magnitude when forming the
operating quantity of the element as follows:
Iop = 3 * (|I_0| - K * |I_1|)
where K = 1/16 and |I_0| = 1/3 * |In|
The positive-sequence restraint allows for more sensitive settings by counterbalancing
spurious
zero-sequence currents resulting from:
• system unbalances under heavy load conditions
• current transformer (CT) transformation errors of during double-line and three-phase
fault
s
• switch-off transients during double-line and three-phase faults
The positive-sequence restraint must be considered when testing for Pickup accuracy and
r
esponse time (multiple of Pickup). The operating quantity depends on how test currents
are injected into the relay (single-phase injection: Iop = 0.9375 * I_injected three-phase
pure zero sequence injection: Iop = 3 * I_injected).
The settings of this function are applied to the neutral current to produce Pickup and Trip
flag
s. The Neutral IOC Pickup flag is asserted, when the neutral current is above the PKP
value. The Neutral IOC Operate flag is asserted if the element stays picked up for the time
defined by the Neutral IOC PKP Delay setting. If the Pickup time delay is set to 0.000
seconds, the Pickup and Operate flags are asserted at the same time. The element drops
from Pickup without operation if the neutral current drops below 97 to 98% of the Pickup
value.
Path:
Setpoints > Protection > Group 1(6) > Current > Neutral IOC 1(2)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
DIRECTION
Range: Disabled, Forward, Reverse
Default: Disabled
PICKUP DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
BLOCK
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
RELAYS
Range: Do Not Operate, Operate
Default: Do Not Operate

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MI-869 and is the answer not in the manual?

GE MI-869 Specifications

General IconGeneral
BrandGE
ModelMI-869
CategoryProtection Device
LanguageEnglish

Related product manuals