IPE300 series engineering VFD Basic operation guidelines
-65-
Function
code
Name
Description
Default
2: PROFIBUS/CANopen/DeviceNet
communication
3: Ethernet communication
4: EtherCAT/Profinet communication
Tens place: indicates whether to enable
switchover during running
0: Disable
1: Enable
P12.00
Type of motor 2
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
P12.01
Rated power of AM 2
0.1–3000.0kW
Model
depended
P12.02
Rated frequency of AM 2
0.01Hz–P00.03(Max. output frequency)
50.00Hz
P12.03
Rated speed of AM 2
1–36000rpm
Model
depended
P12.04
Rated voltage of AM 2
0–1200V
Model
depended
P12.05
Rated current of AM 2
0.8–6000.0A
Model
depended
P12.06
Stator resistance of AM 2
0.001–65.535Ω
Model
depended
P12.07
Rotor resistance of AM 2
0.001–65.535Ω
Model
depended
P12.08
Leakage inductance of
AM 2
0.1–6553.5mH
Model
depended
P12.09
Mutual inductance of AM
2
0.1–6553.5mH
Model
depended
P12.10
No-load current of AM 2
0.1–6553.5A
Model
depended
P12.15
Rated power of SM 2
0.1–3000.0kW
Model
depended
P12.16
Rated frequency of SM 2
0.01Hz–P00.03 (Max. output frequency)
50.00Hz
P12.17
Number of pole pairs of
SM 2
1–50
2