Ensure that these environmental guidelines are followed:
•
The site must be as dust-free as possible, because dust can clog air intake vents and
filters, reducing the efficiency of the switch cooling system.
•
Maintain ambient airflow for normal switch operation. If the airflow is blocked or
restricted, or if the intake air is too warm, the switch might overheat, leading to the
switch temperature monitor shutting down the switch to protect the hardware
components.
Table 32 on page 63 provides the required environmental conditions for normal switch
operation.
Table 32: EX Series Switch Environmental Tolerances
Environment Tolerance
Switch or
device SeismicTemperatureRelative HumidityAltitude
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F (0° C)
through 104° F (40° C) at
altitudes up to 5,000 ft
(1,524 m).
For information about extended
temperature SFP transceivers
supportedonEX2200switches,
see Pluggable Transceivers
Supported on EX2200 Switches.
Normal operation ensured in
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
5,000 feet
(1524 meters)
EX2200-C
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F (0° C)
through 113° F (45° C)
Normal operation ensured in
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet
(3048 meters)
EX2200
(except
EX2200-C
switches)
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F (0° C)
through 104° F (40° C)
Normal operation ensured in
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
5,000 feet
(1524 meters)
EX2300-C
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F (0° C)
through 113° F (45° C)
Normal operation ensured in
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
13,000 feet
(3962.4 meters) at
104° F (40° C) as per
GR-63
EX2300
(except
EX2300-C
switches)
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F (0° C)
through 113° F (45° C)
Normal operation ensured in
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet
(3048 meters)
EX3200
Complies with Zone 4
earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured in the
temperature range 32° F (0° C)
through 113° F (45° C)
Normal operation ensured in
the relative humidity range
10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet
(3048 meters)
EX3300
63Copyright © 2017, Juniper Networks, Inc.