Technical data
3-4

SHB9300CRV EN 2.0
3.3.2 Types 9321 to 9324 with 200 % overcurrent
Type EVS9321-EK EVS9322-EK EVS9323-EK EVS9324-EK
Ratings for operation at a mains: 3 AC / 400V / 50Hz/60Hz
Motor power (4 pole ASM)
P
r
[kW] 0.37 0.75 1.5 3.0
M
o
t
o
r
p
o
w
e
r
(
4
p
o
l
e
A
S
M
)
P
r
[hp] 0.5 1.0 2.0 4.0
Output power U, V, W (8 kHz) S
r8
[kVA] 1.0 1.7 2.7 4.8
Output current (8 kHz)
2)
I
r8
[A] 1.5 2.5 3.9 7.0
Output current (16 kHz)
2)
I
r16
[A] 1.1 1.8 2.9 5.2
Max. output current (8 kHz)
1)
I
max8
[A] 3.0 5.0 7.8 14.0
Max. output current (16 kHz)
1)
I
max16
[A] 2.2 3.6 5.8 10.4
Max. standstill current (8 kHz) I
08
[A] 3.0 5.0 7.8 14.0
Max. standstill current (16 kHz) I
016
[A] 2.2 3.6 5.8 10.4
Ratings for operation at a mains: 3 AC / 480V / 50Hz/60Hz
Motor power (4 pole ASM)
P
r
[kW] 0.37 0.75 1.5 3.0
M
o
t
o
r
p
o
w
e
r
(
4
p
o
l
e
A
S
M
)
P
r
[hp] 0.5 1.0 2.0 4.0
Output power U, V, W (8 kHz) S
r8
[kVA] 1.2 2.1 3.2 5.8
Output current (8 kHz)
2)
I
r8
[A] 1.5 2.5 3.9 7.0
Output current (16 kHz)
2)
I
r16
[A] 1.1 1.8 2.9 5.2
Max. output current (8 kHz)
1)
I
max8
[A] 3.0 5.0 7.8 14.0
Max. output current (16 kHz)
1)
I
max16
[A] 2.2 3.6 5.8 10.4
Max. standstill current (8 kHz) I
08
[A] 3.0 5.0 7.8 14.0
Max. standstill current (16 kHz) I
016
[A] 2.2 3.6 5.8 10.4
1)
The currents apply to a periodical load cycle with 10 seconds overcurrent with the current
mentioned here and 50 seconds base load with 44 % I
rx
Main point for
individual
situations
Settings under
code C0022
Thermal
continuous current
Max. current phase Recovery phase
Continuous power I
max
%
150 % I
rX
100 % I
rX
150 % I
rX
for 60 s 75 % I
rX
for 120 s
Peak power I
max
>
150 % I
rX
70 % I
rX
200 % I
rX
for 10 s 44 % I
rX
for 50 s
2)
The output current INx is only valid for a motor current adjustable under C022 which has not
exceeded 150% rated current (nameplate).
If the maximum current is increased to a value higher than this, the continuous current is
automatically reduced to 70 % of its original value.
Overcurrent diagram:
&
7-245
All other data:
&
3-3
Note!
The change to I
max
> 150 % I
rX
is only possible when the controller is inhibited.
Show/Hide Bookmarks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze EVS9326-EK and is the answer not in the manual?

Lenze EVS9326-EK Specifications

General IconGeneral
BrandLenze
ModelEVS9326-EK
CategoryDC Drives
LanguageEnglish

Related product manuals