Configuration
7-264

SHB9300CRV EN 2.0
7.7.3.16 Parameter error PRO
Purpose
Protects the controller.
Function
Function of LECOM No. 79 (PI)
Someparameters areused for the internal calculation of servo data. The monitoring will be activated
if this calculation detects faulty values.
Reasons:
Data from a high-power controller were transferred to a low-power controller, e. g. the values set for
the motor do not match the controller.
Please contact Lenze, and give them the value indicated under the codes C0300 and C0301.
Function of LECOM No. 75 (PR0)
This fault message is activated if the saved parameter does not correspond to the loaded software
version. Factory setting will then be loaded automatically. All parameter sets must be saved again
manually to acknowledge PR0 (C0003). A fault message can only be acknowledged after saving.
Stop!
It is not enough to save one parameter set.
Features:
l
LECOM
–No.:79(PI)
–No.:75(PR0)
l
Reaction: TRIP (unchangeable)