7.7.3.15 Parameter set error PR1, PR2, PR3, PR4
Purpose
Controller protection
Function
During loading, each of the parameter sets is checked for completeness and correctness. If a
difference should be recognized, the controller changes to the TRIP state. The incorrect parameter
set is displayed (C0168; PR1 = parameter set1 etc.).
At the same time, the default setting is loaded, but not saved (after TRIP-RESET the controller
operates with the default settings, until the setting is changed).
The cause can be a transmission error during the transmission of parameter sets to the controller.
Remedy:
The corresponding parameter set must be reset or transmitted to the controller again.
This interference can also be caused by an interrupt of the transmission of parameter sets by the
operating unit (e.g. by an early disconnection of the operating unit).
Features:
l
LECOM
–No.:72(PR1)
–No.:73(PR2)
–No.:77(PR3)
–No.:78(PR4)
l
Reaction: TRIP (cannot be modified)
Show/Hide Bookmarks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze EVS9326-EK and is the answer not in the manual?

Lenze EVS9326-EK Specifications

General IconGeneral
BrandLenze
ModelEVS9326-EK
CategoryDC Drives
LanguageEnglish

Related product manuals