EasyManuals Logo

Lenze i510 User Manual

Lenze i510
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #101 background imageLoading...
Page #101 background image
7 Fieldbus
Profibus quick start
Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016 101
7.3 Profibus quick start
1. Set an individual node address:
i550: Dip-Switches or Parameter setting P510:1 (0x2341.1)
The active node address will be displayed in P511:1 (0x2342.1)
2. Save the parameters (P700:3, 0x2022:3) and power cycle the drive completely that the configuration takes
effect.
3. Configuration of the host:
Read the device description file (GSD) into the Profibus master.
i
4. Process data configuration
The process data configuration must be configured in the Profibus master configuration tool.
The default configuration in the i550 GSD-file is:
PLC to Drive:
Lenze control word (NetWordIN1) P590:1 (0x4008:1)
Network frequency setpoint 0.01Hz P592:5 (0x400B:5)
16Bit selectable OUT-Data
Drive to PLC:
Lenze status word (NetWordOUT1) P591:1 (0x400A:1)
Actual Speed [0.01 Hz] P593:6 (0x400C:6)
Actual motor current [0.1A] P104 (0x2D88)
i

Table of Contents

Other manuals for Lenze i510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 and is the answer not in the manual?

Lenze i510 Specifications

General IconGeneral
Product CategoryDC Drives
Seriesi510
Protection ClassIP20
CommunicationCANopen, Modbus RTU
Protection FeaturesOvervoltage, Undervoltage
Operating Temperature-10 to +50 °C
Storage Temperature-25 to +70 °C
Humidity5% to 95% (non-condensing)
Control ModeV/f control

Related product manuals