9 Troubleshooting
Error history
Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016 119
9.5 Error history
9.5.1 Error History Keypad
Any time the inverter experiences an Error condition during operation it is captured in the inverter non-volatile
memory. For historical Error tracking purposes the Errors can be viewed in P155.00. This parameter contains the
actual Error codes, the time (in running hours) that the Error occurred and the count of Errors (in case of multiple
instances of the same Error condition). The Error History will retain the 32 most recent Errors.
The data in the Error History is described below:
Error Code
F= Fault
T = Trouble
W = Warning
History Entry Number (01...32)
Lowest number (01) is most recent error
LOC REM MAN AUTO
Time:12d15h13m12s
SET8
0 1 . C T . 0 0 5
LOC REM MAN AUTO
Error memory
SET8
P 1 5 5 . X X
LOC REM MAN AUTO
Over Voltage
SET8
0 1 . F . 3 2 1 0
Press
Time of error in Day, Hours, Minutes, Seconds
(Based on Operating Time P151.03)
Count of occurrences of this error condition
CT = Abbreviation for «Count»
History Entry Number (01..32)
Lowest number (01) is most recent number
Press
Pressing the button will toggle between the two screens described above.
Pressing the and buttons will navigate from Error 01 to Error 32.