6 Function & parameter description
Group 4 – I/O setup
82 Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016
6.6.10 Preset setpoints (Frequency, PID)
The inverter has 15 preset frequency setpoints, 8 preset PID setpoints. They can be selected in two ways:
As default setpoint (Frequency: P201:1, PID: P201:2)
Triggered by digital inputs (P400:18 – 400:21)
The Preset setpoint selection is done by a binary combination of bits triggering the Preset Setpoint Selection
Functions. Combination Example: bit0 and bit2 result in Preset 6
See chapter 6.2.1 Setpoint structure / operation mode, page 36
0.0 ... [20.0] ... 599.0 Hz
Preset frequency setpoint 1
0.0 ... [40.0] ... 599.0 Hz
Preset frequency setpoint 2
0.0 ... [Type code dependent] ...
599.0 Hz
Preset frequency setpoint 3
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 4
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 5
Note:
Also used for Jog FWD
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 6
Note:
Also used for Jog REV
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 7
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 8
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 9
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 10
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 11
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 12
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 13
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 14
0.0 ... [0.0] ... 599.0 Hz
Preset frequency setpoint 15
Process controller preset 1-8
-300.00 ... [0.00] ... 300.00 PUnit