6 Function & parameter description
Group 2 – Basic setup
Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016 49
Power unit - bootloader type
-- ... [Actual value] ... --
6.3.19 Device Name
-- ... [My Device] ... --
Configurable name of inverter
6.3.20 Device Module
-- ... [Actual value] ... --
Type code of control unit
Example: I5CA500200V000000S
Power unit - product code
-- ... [Actual value] ... --
Type code of power unit
Example: I5DAE222F10V1000S
Control unit - serial number
-- ... [Actual value] ... --
Power unit - serial number
-- ... [Actual value] ... --
6.3.21 Additional status
Bit # description:
0: Full write access protected
1: Write access only for favorites
Actual status of access protection
0 = No protection
1 = Only read access to all parameters
2 = Only read & write access on favorites group
0: User settings
1: Reset 60 Hz Settings
2: Reset 50 Hz Settings
3: OEM Settings
Actual loaded parameter settings
6.4 Group 2 – Basic setup
6.4.1 Default control source
See chapter “6.2.1 Setpoint structure / operation mode”, page 36
See chapter “6.2.2 Control Source”, page 38
Defines the default Control Source for Start, Stop and Rotation direction.
The inverter can be controlled from several sources such as terminals
(Digital Inputs), Fieldbus or Keypad.
0: Flexible Control
Start / Stop and rotation direction configured in P400.xx