8 Drive Profile (Fieldbus)
Profibus quick start
Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016 103
8 Drive Profile (Fieldbus)
Several command words, status and setpoint are available to control the drive from remote:
CIA402 (Predefined mapping) Used for EtherCAT/CAN
AC drive profile (Predefined mapping) Used for EtherNet/IP
Lenze Legacy (Predefined mapping)
Netword IN/Out (Individual mapping)
Control / Status
Individual mapping Lenze Legacy
Communication DRIVE CONTROL
Control items:
- Control
- Status
- Setpoint
- Actual speed
Note:
- Activate network
control with P400:37
(Network enable)
- Activate network
setpoint by selection in
in Pt P201:1 (Default
speed setpoint) or by
control word
Modbus
Modbus Register Mapping
- 24x Mappable registers
- Fixed Mapping Common
Par
Network
PROFIBUS
PDO Mapping:
Mapping is done in
Profibus Master (HW-
Config) and send to the
drive automatically
CAN
PDO Mapping:
- RPDO: 0x1601-2
- TPDO: 0x1A00-2
Config for PDO
(COB-ID, Type, etc.)
RPDO: 1400:x -1402:x
TPDO: 1800:x -1802:x
MAPPING P505:1-16
NetWordOut1 0x400A:1
Drive States
Mapping P420:10-25
Configuration /
Parameter
Asyclic / Direct parameter access
Lenze C150 Status Word 0x400B:2
Actual Speed ABS [0.1Hz] 0x400C:3
Actual Speed ABS [RPM] 0x400C:4
Actual Speed ABS [0.01 Hz] 0x400C:5
Network Speed Setpoint ABS[0.1Hz] 0x400B:3
Network Speed Setpoint ABS[RPM] 0x400B:4
Network Speed Setpoint ABS[0.01Hz] 0x400B:5
Network Speed Setpoint Signed [0.1Hz] 0x400B:6
C135 Control Word 0x400B:2
NetWordIn1 0x4008:1
Function Trigger bits
NetWordIn2 0x4008:2
Switch Digital Outputs
NetWordIn3 0x4008:3
Source for AO1/AO2
NetWordIn4 0x4008:4
Source for AO1/AO2
MAPPING P440:2, P441:2
ß
ß
ß
FIXED
MAPPING P420:1-25
FIXED
FIXED
MAPPING P440:2, P441:2
AC Drive CIA402
AC Drive Status Word 0x400C:1
AC Drive Control Word 0x400B:1
CIA402 Drive Control Word 0x6040
CIA402 Drive Status Word 0x6041
CIA402 Actual velocity [RPM] 0x6044
CIA402 Target velocity [RPM] 0x6042
ß
ß
ß

Table of Contents

Other manuals for Lenze i510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 and is the answer not in the manual?

Lenze i510 Specifications

General IconGeneral
Product CategoryDC Drives
Seriesi510
Protection ClassIP20
CommunicationCANopen, Modbus RTU
Protection FeaturesOvervoltage, Undervoltage
Operating Temperature-10 to +50 °C
Storage Temperature-25 to +70 °C
Humidity5% to 95% (non-condensing)
Control ModeV/f control