8 Drive Profile (Fieldbus)
AC Drive Profile
Lenze · Inverter i510 / i550 - Cabinet · Operation Manual · 0.4 EN · 02/2016 109
8.3 AC Drive Profile
This chapter describes the AC Drive Format
This Format is normally used for EtherNet/IP
8.3.1 Control word
0x400B:1 P592:1 AC Drive control word
Some of the bits will be ignored if bit5 NetCtrl bit is not set, see table below for details
Run Forward - see transition table below for exact logic
NOTE: Bit processed only when NetCtrl = 1
Run Reverse - see transition table below for exact logic
NOTE: Bit processed only when NetCtrl = 1
Reset existing fault. Only on transition from 0->1
Control from Network (NetCtrl)
If bit5 NetCtrl is 1 and Network Enable 0x2631:37 = 114 (Network Con-
trolEnableRequest.Bit): All bits of this control word are processed.
If bit5 NetCRl is 0 or Network Enable 0x2631:37 is not asserted: Con-
trol bits 0, 1, 12, 13, 14, 15 are NOT processed; their states are ignored
and the drive is in local control with functions triggered by settings in
0x2631 (P400)
If NetRef = 1
Network Setpoint becomes active drive setpoint. Network Setpoint
could be speed, frequency, PID setpoint or Torque setpoint
If NetRef = 0
Selected default setpoint 0x2860:1-2 (0x201:1-2) is active.
Note: Bit 6 can also be used to set network as setpoint source in ter-
minal mode. See 0x2631:17 (P400:17)
NOTE: Bit processed only when NetCtrl = 1
NOTE: Bit processed only when NetCtrl = 1
NOTE: Bit processed only when NetCtrl = 1
NOTE: Bit processed only when NetCtrl = 1