Multi−axis controllers
Rated data
Operation in 400−V−AC system
4
175
EDS94SPP101 EN 10.2
4.4.3 Operation in 400−V−AC system
Mains Volta
g
e Volta
g
e ran
g
e Fre
q
uenc
y
ran
g
e
Voltage
U
DC
[V]
Voltage
range
U
DC
[V]
Frequency
range
f [Hz]
2/PE DC 565 455 − 0 % ... 620 + 0 %
Input current at I
aN8
Output power Motor power
(typical)
(without external mains
choke)
U, V, W 4−pole ASM
Type I
DC
[A] S
aN
[kVA] P
aN
[kW] P
aN
[hp]
E94AMxE0024 2.6 0.9 0.37 0.5
E94AMxE0034 4.3 1.6 0.75 1.0
E94AMxE0044 6.7 2.5 1.5 2.0
E94AMxE0074 12.1 4.4 3.0 4.0
E94AMxE0094 15.4 5.8 4.0 5.0
E94AMxE0134 20.6 8.1 5.5 7.5
E94AMxE0174 25.7 10.3 7.5 11.0
E94AMxE0244 35.5 14.7 11.0 15.0
E94AMxE0324 48.0 20.0 15.0 20.4
E94AMxE0474 71.0 29.3 22 29
E94AMxE0594 89.0 36.8 30 40
Output currents [A] at switching frequency
2 kHz 4 kHz 8 kHz 16 kHz
I
aN2
I
aM2
I
aN4
I
aM4
I
aN8
I
aM8
I
aN16
E94AMxE0024 1.9 6.0 1.9 6.0 1.5 4.8 1.1
E94AMxE0034 3.1 10.0 3.1 10.0 2.5 8.0 1.9
E94AMxE0044 5.0 16.0 5.0 16.0 4.0 12.8 3.0
E94AMxE0074 8.8 21.0 8.8 21.0 7.0 16.8 5.3
E94AMxE0094 11.7 28.0 11.7 28.0 9.3 22.4 7.0
E94AMxE0134 16.3 39.0 16.3 39.0 13.0 31.2 9.8
E94AMxE0174 20.6 49.5 20.6 49.5 16.5 39.6 12.4
E94AMxE0244 29.4 70.5 29.4 70.5 23.5 56.4 17.6
E94AMxE0324 40.0 76.8 40.0 76.8 32.0 76.8 16.0
E94AMxE0474 47.0 94.0 47.0 94.0 41.0 82.0 21.5
E94AMxE0594 59.0 118 59.0 118 41.0 82.0 21.5
I
aN2
Rated value of permanent output current at a frequency of 0 Hz
I
aM2
Maximum output current (overload current) at frequency 0 Hz
Periodic load change of 0.5 s with I
aM2
and recovery time of 4.5 s with
75% I
aN2
I
aN4
, I
aN8,
I
aN16
Rated value of continuous output current at a frequency of 5 Hz
(reduce to 0.66 * I
aNx
for 0 ... 5 Hz)
I
aM4
, I
aM8
Maximum output current (overload current) at frequency 5 Hz
(reduce to 0.66 * I
aMx
for 0 ... 5 Hz)
Periodic load change of 0.5 s with I
aMx
and recovery time of 4.5 s with
75% I
aNx
Can be achieved using the setting "x kHz fixed" in C00018
bold Nominal value I
aN
4)
Depending on the heatsink temperature, the mains voltage and the motor
cable length, the switching frequency can be changed even at smaller currents.

Table of Contents

Other manuals for Lenze L-force 9400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze L-force 9400 and is the answer not in the manual?

Lenze L-force 9400 Specifications

General IconGeneral
BrandLenze
ModelL-force 9400
CategoryDC Drives
LanguageEnglish

Related product manuals