5. PARAMETERS
5.12 (N) Operation via communication and its settings
3
4
5
5
5
6
7
8
9
10
5.12.10 Backup/restore
• The GOT can be used for backing up inverter parameters and the data used in the PLC function of inverter.
• The backup data stored in the GOT can be used to restore the data in the inverter.
*1 The setting is available in the inverter on which the FR-A8NCE is installed.
Connected devices
• To enable backup/restore, connect either the general-purpose inverter with the FR-A8NCE to a programmable controller
(master station) via the CC-Link IE Field Network.
NOTE
• The backup/restore function is enabled only when the inverter is connected to a master station programmable controller.
• For details on the connected devices, refer to the GOT2000 Series User's Manual (Monitor).
Data to be backed up and restored
• The following data can be backed up and restored. The data other than listed below cannot be backed up or restored.
Pr. Name Initial value Setting range Description
434
N110
*1
Network number (CC-Link IE) 0 0 to 255 Enter the network number of the inverter.
435
N111
*1
Station number (CC-Link IE) 0 0 to 255 Enter the station number of the inverter.
Item
Inverter parameters
Parameters used for activating the PLC function
Programs (including SFCs) used in the PLC function
Global device comment information used in the PLC function
Function block source information
GOT2000
MELSEC iQ-R
CC-Link IE Field NetworkEthernet
Backup
Restoration
FR-F860 (with the FR-A8NCE installed)