5
îš‹ Motor Autotuning: T
T1: Autotuning 1
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Closed
Loop
Vector
(PM)
Display
T1-01
Autotuning
mode selection
Sets the autotuning mode.
0:Rotating autotuning
1:Non-rotating autotuning
2:Non-rotating autotuning for
line-to-line resistance only
4: Encoder offset tuning
0 to 2
i
No
Yes
(2)
Yes
(1)
Yes
(1)
-
701H 4-4
Tuning Mode Sel 0 or 4 - - -
Yes
(4)
T1-02
Motor output
power
Sets the output power of the
motor in kilowatts.
0.00 to
650.00
3.70
kW
*1
*1. The factory setting depends on the Inverter capacity. (The value for a 200 V Class Inverter for 3.7 kW is given.)
No Ye s Ye s Yes - 70 2H 4-4
Mtr Rated Power
T1-03
Motor rated volt-
age
Sets the rated voltage of the
motor.
0 to
255.0
*2
*2. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
190.0 V
*2
No - Yes Yes - 703H 4-4
Rated Voltage
T1-04
Motor rated cur-
rent
Sets the rated current of the
motor.
1.75 to
35.00
*3
*3. The setting range is from 10% to 200% of the Inverter rated output current. (The value for a 200 V Class Inverter for 0.4 kW is given.)
14.00 A
*1
No Ye s Ye s Yes - 70 4H 4-4
Rated
Current
T1-05
Motor rated fre-
quency
Sets the rated frequency of the
motor.
0 to
120.0
50.0 Hz No - Yes Yes - 705H 4-4
Rated Frequency
T1-06
Number of motor
poles
Sets the number of motor poles.
2 to 48
poles
4 poles No - Yes Yes - 706H 4-4
Number of Poles
T1-07
Motor base
speed
Sets the base speed of the motor
in r/min.
0 to
24000
1450
r/min
No - Yes Yes - 707H -4-4
Rated Speed
T1-08
Number of PG
pulses
Sets the number of PG pulses
per revolution.
0 to
60000
1024 No - - Yes - 708H 4-4
PG Pulses/Rev
T1-09
No load current
Sets the no load current of
motor.
0.0 to
13.99
*1
E2-03 No - Yes Yes - 709H 4-4
No load current