10-5
10
User Constants
The factory settings of each parameter are given in the following table. They are for a 200 V Class Inverter
with 3.7 kW.
No. Name
Factory
Setting
Setting
A1-00 Language selection for Digital Operator display 0
A1-01 Parameter access level 2
A1-02 Control method selection 0
A1-03 Initialize 0
A1-04 Password 0
A1-05 Password setting 0
A2-01 to
A2-32
User specified parameters –
b1-01 Reference source selection 0
b1-02 RUN command source selection 1
b1-06 Control input scan 1
b1-08 Run command selection in programming modes 1
b2-08 Magnetic flux compensation volume 0%
b4-01 Timer function ON-delay time 0.0 sec.
b4-02 Timer function OFF-delay time 0.0 sec.
b6-01 Dwell frequency at start 0.0 Hz
b6-02 Dwell time at start 0.0 sec.
b6-03 Dwell frequency at stop 0.0 Hz
b6-04 Dwell time at stop 0.0 sec.
C1-01 Acceleration time 1 10.0 sec.
C1-02 Deceleration time 1
1.5 s
C1-03 Acceleration time 2
C1-04 Deceleration time 2
C1-05 Acceleration time 3
C1-06 Deceleration time 3
C1-07 Acceleration time 4
C1-08 Deceleration time 4
C1-09 Emergency stop time
C1-10 Accel/decel time setting unit 1
C1-11 Accel/decel time switching frequency 0.0 Hz
C2-01 S-curve characteristic time at acceleration start 0.5 sec.
C2-02 S-curve characteristic time at acceleration end 0.5 sec.
C2-03 S-curve characteristic time at deceleration start 0.5 sec.
C2-04 S-curve characteristic time at deceleration end 0.5 sec.
C2-05 S-curve Characteristic time below leveling speed 0.50 sec.
C3-01 Slip compensation gain 1.0
C3-02 Slip compensation delay time 2000 msec
C3-03 Slip compensation limit 200%
C3-04 Slip compensation selection during regeneration 1
C3-05 Output voltage limit operation selection 1
C4-01 Torque compensation gain 1.00
C4-02 Torque compensation delay time constant
200 msec
*1
C4-03 Starting torque compensation (FWD) 0.0%
C4-04 Starting torque compensation (REV) 0.0%
C4-05 Starting torque compensation time constant 10 msec