User Constant Tables
5-
79
U: Monitor Constants
The following settings are made with the monitor constants (U constants): Setting constants for monitoring in
drive mode.
Status Monitor Constants: U1
The constants used for monitoring status are listed in the following table.
* 1. The unit is set in o1-03 (frequency units of reference setting and monitor).
* 2. The unit differs according to the Inverter capacity. (The unit is 0.01 A for an Inverter capacity of 0.4 to 7.5 kW, and 0.1 A for an Inverter capacity of
11 kW and larger.)
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO-
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
U1-01
Frequency
reference
Monitors/sets the fre-
quency reference value.
*1
10 V: Max. frequency
(-10 to 10 V possible)
0.01
Hz
AAAAA40H
Frequency
Ref
U1-02
Output
frequency
Monitors the output fre-
quency.
*1
10 V: Max. frequency
(-10 to 10 V possible)
0.01
Hz
AAAAA41H
Output Freq
U1-03
Output
current
Monitors the output cur-
rent.
10 V: Inverter rated output
current
(0 to +10 V, absolute value
output)
0.01
A
*2
AAAAA42H
Output
Current
U1-04
Control
method
Checks the current control
method.
(Cannot be output.) A A A A A 43H
Control
Method
U1-05
Motor speed
Monitors the detected
motor speed.
*1
10 V: Max. frequency
(-10 to 10 V possible)
0.01
Hz
NoAAAA44H
Motor Speed
U1-06
Output
voltage
Monitors the output volt-
age reference value in the
Inverter.
10 V: 200 VAC (400 VAC)
(0 to +10 V output)
0.1 V A A A A A 45H
Output
Voltage
U1-07
DC bus
voltage
Monitors the main DC
voltage in the Inverter.
10 V: 400 VDC (800 VDC)
(0 to +10 V output)
1 V A A A A A 46H
DC Bus
Voltage
U1-08
Output
power
Monitors the output power
(internally detected value).
10 V: Inverter capacity for
V/f control
Motor capacity (E2-
11) for vector control
(-10 to 10 V possible)
0.1
kW
AAAAA47H
Output
kWatts
U1-09
Torque
reference
Monitor in internal torque
reference value for vector
control.
10 V: Motor rated torque
(-10 to 10 V possible)
0.1% No No A A A 48H
Torque
Reference
TOE-S616-60.1.book 79 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals