Acceleration and Deceleration Characteristics
6-
23
Preventing the Motor from Stalling During Acceleration (Stall Prevention
During Acceleration Function)
The Stall Prevention During Acceleration function prevents the motor from stalling if a heavy load is placed
on the motor, or sudden rapid acceleration is performed.
If you set L3-01 to 1 (enabled) and the Inverter output current exceeds the -15% level of the set value in L3-
02, the acceleration rate will begin to slow down. When L3-02 is exceeded, acceleration will stop.
If you set L3-01 to 2 (optimum adjustment), the motor current accelerates to the value set in L3-02. With this
setting, the acceleration time setting is ignored.
Related Parameters
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
L3-01
Stall preven-
tion selection
during accel
0: Disabled (Acceleration as set.
With a heavy load, the motor
may stall.)
1: Enabled (Acceleration
stopped when L3-02 level is
exceeded. Acceleration starts
again when the current is
returned.)
2: Intelligent acceleration mode
(Using the L3-02 level as a
basis, acceleration is
automatically adjusted. Set
acceleration time is
disregarded.)
0 to 2 1 No A A A No No 48FH
StallP Accel Sel
L3-02
Stall preven-
tion level
during accel
Effective when L3-01 is set to 1
or 2.
Set as a percentage of Inverter
rated current.
Usually setting is not necessary.
The factory setting reduces the set
values when the motor stalls.
0 to
200
150% No A A A No No 490H
StallP Accel
Lvl
L3-03
Stall preven-
tion limit
during accel
Sets the lower limit for stall pre-
vention during acceleration, as a
percentage of the Inverter rated
current, when operation is in the
frequency range above E1-06.
Usually setting is not necessary.
0 to
100
50% No A A A No No 491H
StallP CHP Lvl
TOE-S616-60.1.book 23 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals