Detecting Motor Torque
If an excessive load is placed on the machinery (overtorque) or the load is suddenly lightened (undertorque),
you can output an alarm signal to multi-function output terminal M1-M2, P1-PC, P2-PC, P3-C3, or P4-C4.
To use the overtorque/undertorque detection function, set B, 17, 18, 19 (overtorque/undertorque detection NO/
NC) in one of the following constants: H2-01 to H2-05 (multi-function output terminals M1-M2, P1-PC, P2-
PC, P3-C3, and P4-C4 function selection).
The overtorque/undertorque detection level is the current level (Inverter rated output current 100%) in V/f
control, and the motor torque (motor rated torque 100%) in vector control.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
L6-01
Torque detec-
tion selection 1
0: Overtorque/undertorque
detection disabled.
1: Overtorque detection only
with speed agreement;
operation continues after
overtorque (warning).
2: Overtorque detected
continuously during
operation; operation continues
after overtorque (warning).
3: Overtorque detection only
with speed agreement; output
stopped upon detection
(protected operation).
4: Overtorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
5: Undertorque detection only
with speed agreement;
operation continues after
overtorque (warning).
6: Undertorque detected
continuously during
operation; operation continues
after overtorque (warning).
7: Undertorque detection only
with speed agreement; output
stopped upon detection
(protected operation).
8: Undertorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
0 to 8 0 No A A A A A 4A1H
Torq Det 1 Sel
L6-02
Torque detec-
tion level 1
Open-loop vector control: Motor
rated torque is set as 100%.
V/f control: Inverter rated current
is set as 100%.
0 to
300
150% No A A A A A 4A2H
Torq Det 1 Lvl
TOE-S616-60.1.book 54 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals