6-
167
Related Constants
Setting Precautions
Always set b1-01 (Reference selection) to 1 (control circuit terminal) when using the AI-14B for three chan-
nels of independent inputs. When this is done, H1-01 to H1-10 (multi-function contact inputs) cannot be set to
2 (Option/Inverter selection).
Using a Digital Reference Board
When using a DI-08 or DI-16H2 Digital Reference Board, set b1-01 (Reference selection) to 3 (Option board).
The DI-16H2 can be used to set a frequency using a 16-bit digital reference. The DI-08 can be used to set a
frequency using a 8-bit digital reference.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
F2-01
Bi-polar or uni-
polar input
selection
Sets the functions for channel 1 to
3 that are effective when the AI-
14B Analog Reference Board is
used.
0: 3-channel individual (Chan-
nel 1: terminal A1, Channel 2:
terminal A2, Channel 3: termi-
nal A3)
1: 3-channel addition (Addition
values are the frequency refer-
ence)
When set to 0, select 1 for b1-01.
In this case the multi-function
input “Option/Inverter selection”
cannot be used.
0 or 1 0 No A A A A A
38FH
AI-14 Input Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
F3-01
Digital input
option
Sets the Digital Reference Board
input method.
0: BCD 1% unit
1: BCD 0.1% unit
2: BCD 0.01% unit
3: BCD 1 Hz unit
4: BCD 0.1 Hz unit
5: BCD 0.01 Hz unit
6: BCD special setting (5-digit
input)
7: Binary input
6 is only effective when the DI-
16H2 is used.
0 to 7 0 No A A A A A 390H
DI Input
TOE-S616-60.1.book 167 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals