-50
Preventing Motor Stalling During Operation
Stall prevention during operation prevents the motor from stalling by automatically lowering the Inverter's
output frequency when a transient overload occurs while the motor is operating at a constant speed.
Stall prevention during operation is enabled only during V/f control. If the Inverter output current continues to
exceed the setting in constant L3-06 for 100 ms or longer, the motor speed is reduced. Set whether to enable or
disable deceleration time using constant L3-05. Set the deceleration time using C1-02 (Acceleration time 1) or
C1-04 (Acceleration Time 2).
If the Inverter output current reaches the set value in L3-06 - 2% (Inverter Rated Output Current), the motor
will accelerate again at the frequency set or the acceleration time set.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
L3-05
Stall preven-
tion selection
during running
0: Disabled (Runs as set. With a
heavy load, the motor may
stall.)
1: Deceleration time 1 (the
deceleration time for the stall
prevention function is C1-02.)
2: Deceleration time 2 (the
deceleration time for the stall
prevention function is C1-04.)
0 to 2 1 No A A No No No 493H
StallP Run Sel
L3-06
Stall preven-
tion level
during running
Effective when L3-05 is 1 or 2.
Set as a percentage of the Inverter
rated current.
Usually setting is not necessary.
The factory setting reduces the set
values when the motor stalls.
30 to
200
160% No A A No No No 494H
StallP Run
Level
TOE-S616-60.1.book 50 ージ 017年8月4日 金曜日 午後3時41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals