Individual Functions
6-
129
Torque Control
With flux vector control or open-loop vector 2 control, the motor's output torque can be controlled by a torque
reference from an analog input. To control torque, set d5-01 to 1 or set multi-function contact inputs H1-
to 71 (Speed/Torque control) and turn ON the contact.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
d5-01
Torque control
selection
0: Speed control (C5-01 to C5-
07)
1: Torque control
This function can be used in flux
vector control and open-loop vec-
tor 2 control. To use the function
for switching between speed and
torque control, set to 0 and set the
multi-function input to “speed/
torque control change.”
0 or 1 0 No No No No A A 29AH
Torq Control
Sel
d5-02
Torque
reference delay
time
Set the torque reference filter pri-
mary delay time in ms units.
This function can be used to
adjust the noise of the torque con-
trol signal or the responsiveness
with the host controller. When
oscillation occurs during torque
control, increase the set value.
0 to
1000
0
*
No No No No A A 29BH
Torq Ref Filter
d5-03
Speed limit
selection
Set the speed limit command
method for the torque control
method.
1: The analog input limit from a
frequency reference
2: Limited by d5-04 constant set-
ting values.
1 or 2 1 No No No No A A 29CH
Speed Limit Sel
d5-04
Speed limit Set the speed limit during torque
control as a percentage of the
maximum output frequency.
This function is enabled when d5-
03 is set to 2. Directions are as
follows:
+: Run Command direction
-: Opposite of Run Command
-120
to
+120
0NoNoNoNoAA29DH
Speed Lmt
Value
d5-05
Speed limit bias Set the speed limit bias as a per-
centage of the maximum output
frequency.
Bias is applied to the specified
speed limit. It can be used to
adjust the margin for the speed
limit.
0 to
120
10 No No No No A A 29EH
Speed Lmt Bias
TOE-S616-60.1.book 129 ページ 017年8月4日 金曜日 午後3時41分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 Series and is the answer not in the manual?

YASKAWA Varispeed G7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7 Series
CategoryInverter
LanguageEnglish

Related product manuals