Machine Protection
6-
43
Machine Protection
This section explains functions for protecting the machine.
Reducing Noise and Leakage Current
The switching frequency of the Inverter’s output transistor can be changed to reduce carrier noise and leakage
current from the motor.
Related Constants
* 1. The factory settings depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 2. The setting ranges depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 3. This constant can be monitored or set only when F is set for C6-02.
* 4. Displayed in Quick Programming Mode when motor 2 is set for a multi-function input.
* 5. The maximum output frequency depends on the setting for the carrier frequency (refer to page 6-44).
* 6. This setting is for software versions PRG 1040 and later. The factory setting with software versions PRG 1039 and earlier depends on the Inverter
capacity.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
C6-02
Carrier fre-
quency
selection
Select carrier wave fixed pattern.
Select F to enable detailed settings using
constants C6-03 to C6-07.
1 to F
*2
6
*1
No Q Q Q Q
No
*4
224H
Carrier
Freq Sel
C6-03
*3
Carrier
frequency
upper limit
Set the carrier frequency upper limit and
lower limit in kHz units.
The carrier frequency gain is set as fol-
lows:
With the vector control method, the
upper limit of the carrier frequency is
fixed in C6-03.
K is a coefficient that depends on the
setting of C6-03.
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
2.0 to
15.0
*2 *5
15.0
kHz
*1
No A A A A No 225H
Carrier
Freq Max
C6-04
*3
Carrier
frequency
lower limit
0.4 to
15.0
*2 *5
15.0
kHz
*1
No A A No No No 226H
Carrier
Freq Min
C6-05
*3
Carrier fre-
quency
propor-
tional gain
00 to
99
00 No A A No No No 227H
Carrier
Freq Gain
C6-11
Carrier fre-
quency
selection
for open-
loop vector
2 control
Select the carrier frequency when open-
loop vector 2 control is used.
1: 2 kHz
2: 4 kHz
3: 6 kHz
4: 8 kHz
1 to 4
1
*6
No
No
*4
No
*4
No
*4
No
*4
Q22DH
Carrier
Freq Sel
Carrier frequency
Output frequency x (C6-05) x K
(Max. output frequency)
Output
frequency
TOE-S616-60.1.book 43 ページ 2017年8月4日 金曜日 午後3時41分